LCDI can cut the load circuit timely, make the leakage current in the cut-circuit will not Beyond 5mA
When the leakage fault between shield wire and L-wire happened, LCDI can cut the Circuit before 8.5
cycles disengaging in 0.5 second
L-G, N-G and load-end can sustain 1240V endurance test in a minute
120V LCDI accommodation: 102-132V AC, 240V LCDI
Accommodation: 204-264V AC
Surge-proof function: can sustain 4/2kA combined-surge attack, surge is applied at phase angels of 90 and 270, five applications are at positive, five applications are at negative
Total surge cycles are 20
Over-load function: can sustain 50 over-load tests, whose test current is 6 time of the Rate current
Features:
Leakage current detection interrupter
Meets UL 1699 requirement
Meets UL 498 and UL 484 requirement
UL and CUL file No E257183